Microsoft KB Archive/102711

From BetaArchive Wiki
The printable version is no longer supported and may have rendering errors. Please update your browser bookmarks and please use the default browser print function instead.
Knowledge Base


How to Create a UPS Cable for the APC Smart-UPS

Article ID: 102711

Article Last Modified on 10/31/2006



APPLIES TO

  • Microsoft Windows NT Advanced Server 3.1
  • Microsoft Windows NT Workstation 3.1
  • Microsoft Windows NT Advanced Server 3.1



This article was previously published under Q102711

The APC Smart-UPS series models 900, 900XL, 1250, and 2000 systems include a standard RS-232 line failure output and UPS shutdown input. The low battery signal, however, is not a standard RS-232 signal and requires special configuration for use with Windows NT.

For RS-232 outputs and inputs, the line failure, low battery, and UPS shutdown signals can be connected from the UPS to one of the computers RS-232 (serial) ports. Because the low battery signal generated by the APC Smart-UPS is an open collector output, it must be pulled up to a common reference voltage by means of a pullup resistor.

Following is the configuration for a cable that can be used with the APC Smart-UPS series, including the implementation of the pullup resistor.

   DB9 9 Pin Female Connector       DB9 9 Pin Male Connector
    (to PC serial port)              (to UPS connector)
          Pin #5------ Ground ----------Pin #4
          Pin #8------ Power Failure--- Pin #2
          Pin #4------ UPS Shutdown---- Pin #1
          Pin #1------ Low Battery----- Pin #5 --[10k ohm]-- Pin #8

The above diagram indicates that Pin #5 on the PC serial port should be connected directly to pin 4 on the UPS side, pin 8 to pin 2, pin 4 to pin 1, and pin 1 to pin 5. In addition, pins 5 and 8 on the same side (the UPS side) have a 10k ohm (10,000 ohm) resistor connected between them. This resistor serves to pull the voltage on this non-RS-232 output high until an actual low voltage is generated by a low battery condition.

With the above cable, the following polarities should be set in the UPS section of the Control Panel:

   Power failure signal: Positive
   Low battery signal:   Negative
   Remote UPS shutdown:  Positive

REFERENCES

American Power Conversion Smart UPS 900, 900XL, 1250 & 2000 Owners Manual

The APC Smart-UPS is manufactured by American Power Conversion, a vendor independent of Microsoft; we make no warranty, implied or otherwise, regarding this products' performance or reliability.

Keywords: kbhardware KB102711